For building managers, facilities managers, and responsible persons
| # | Check Item | Pass | Fail | Notes / Severity |
|---|---|---|---|---|
| 1.1 | Door leaf in good condition — no damage, holes, or delamination Check both faces and all edges |
|||
| 1.2 | Certification label / plug present and legible Third-party cert mark (e.g. BWF-Certifire, BM TRADA) |
|||
| 1.3 | Gaps between door and frame within 3mm tolerance Check top, latch side, hinge side. Threshold max 8mm (or 3mm if smoke seal required) |
|||
| 1.4 | Intumescent strips present and in good condition Continuous run, not painted over, not missing sections |
|||
| 1.5 | Cold smoke seals present and in good condition Required on all fire doors in residential common areas |
|||
| 1.6 | Minimum 3 hinges fitted, all fire-rated (CE marked) Securely fixed, no missing screws, not bent or worn |
|||
| 1.7 | Self-closing device fitted and operational Door must close fully from any angle and latch into frame |
|||
| 1.8 | Glazing is fire-rated and in good condition Check for Georgian wired, Pyran, or marked fire glass. No cracks or failed seals |
|||
| 1.9 | "Fire Door Keep Shut" or "Fire Door Keep Locked" sign present Legible, correct type, fixed to both sides if required |
|||
| 1.10 | Frame securely fixed and in good condition No loose fixings, splits, rot, or gaps between frame and wall |
| # | Check Item | Pass | Fail | Notes / Severity |
|---|---|---|---|---|
| 2.1 | Door closes fully into frame under its own power From fully open, 45°, and 15° positions |
|||
| 2.2 | Door latches securely — no bounce-back Latch must engage in strike plate |
|||
| 2.3 | No obstructions preventing full closure Wedges, door stops, hold-open devices (unless linked to fire alarm) |
|||
| 2.4 | Hold-open device (if fitted) is linked to fire alarm and releases on activation Test by triggering alarm or manual release |
|||
| 2.5 | Door opens freely — no binding, dragging, or sticking |
| # | Check Item | Pass | Fail | Notes / Severity |
|---|---|---|---|---|
| 3.1 | Service penetrations through fire walls/floors are sealed Pipes, cables, ducts, trays — check both sides of barrier |
|||
| 3.2 | Fire stopping material is appropriate and correctly installed Intumescent sealant, batt, collars, wraps — third-party certified |
|||
| 3.3 | Riser cupboards — fire stopping intact at each floor level No gaps, no missing fire stopping, access panels in place |
|||
| 3.4 | Ceiling voids — compartment barriers extend to underside of slab No gaps above corridor/compartment walls |
|||
| 3.5 | No unauthorised alterations breaching compartment lines New installations, removed walls, unplugged openings |
| # | Check Item | Pass | Fail | Notes / Severity |
|---|---|---|---|---|
| 4.1 | Escape routes clear and unobstructed No storage, furniture, or items narrowing corridors below 1m |
|||
| 4.2 | Final exit doors open without a key from inside Panic hardware / push bars operational |
|||
| 4.3 | Emergency lighting operational Check indicator LEDs, last test date recorded |
|||
| 4.4 | Fire exit and directional signs visible and illuminated Green running man signs at every change of direction |
| # | Check Item | Pass | Fail | Notes / Severity |
|---|---|---|---|---|
| 5.1 | "Fire Door Keep Shut" on every fire door without a hold-open device | |||
| 5.2 | "Fire Door Keep Locked" on every locked fire door | |||
| 5.3 | Fire action notices posted in visible locations At main entrance, each floor, near fire alarm call points |
|||
| 5.4 | Fire extinguisher ID signs present and correct type indicated |
| # | Check Item | Yes | No | Notes / Action Required |
|---|---|---|---|---|
| 6.1 | Current fire risk assessment on file (within last 12 months or after significant change) | |||
| 6.2 | Fire door inspection records on file | |||
| 6.3 | Remedial works log — actions tracked and closed out | |||
| 6.4 | Fire alarm test records up to date (weekly test) | |||
| 6.5 | Emergency lighting test records up to date (monthly flick test, annual 3-hour test) | |||
| 6.6 | Fire evacuation drill conducted and recorded (at least annually) |