🛡 Fire Compliance Checklist

For building managers, facilities managers, and responsible persons

DE Fire Compliance
defirecompliance.co.uk
info@defirecompliance.co.uk
+44 7770 871782
Critical — Immediate action required
Major — Action within 7 days
Minor — Action within 30 days
Advisory — Recommended improvement
1. Fire Door — Visual Inspection Ref: BS 8214:2016 / Fire Safety Order 2005
# Check Item Pass Fail Notes / Severity
1.1 Door leaf in good condition — no damage, holes, or delamination
Check both faces and all edges
1.2 Certification label / plug present and legible
Third-party cert mark (e.g. BWF-Certifire, BM TRADA)
1.3 Gaps between door and frame within 3mm tolerance
Check top, latch side, hinge side. Threshold max 8mm (or 3mm if smoke seal required)
1.4 Intumescent strips present and in good condition
Continuous run, not painted over, not missing sections
1.5 Cold smoke seals present and in good condition
Required on all fire doors in residential common areas
1.6 Minimum 3 hinges fitted, all fire-rated (CE marked)
Securely fixed, no missing screws, not bent or worn
1.7 Self-closing device fitted and operational
Door must close fully from any angle and latch into frame
1.8 Glazing is fire-rated and in good condition
Check for Georgian wired, Pyran, or marked fire glass. No cracks or failed seals
1.9 "Fire Door Keep Shut" or "Fire Door Keep Locked" sign present
Legible, correct type, fixed to both sides if required
1.10 Frame securely fixed and in good condition
No loose fixings, splits, rot, or gaps between frame and wall
2. Fire Door — Functional Test
# Check Item Pass Fail Notes / Severity
2.1 Door closes fully into frame under its own power
From fully open, 45°, and 15° positions
2.2 Door latches securely — no bounce-back
Latch must engage in strike plate
2.3 No obstructions preventing full closure
Wedges, door stops, hold-open devices (unless linked to fire alarm)
2.4 Hold-open device (if fitted) is linked to fire alarm and releases on activation
Test by triggering alarm or manual release
2.5 Door opens freely — no binding, dragging, or sticking
3. Compartmentation & Fire Stopping Ref: Approved Document B / BS 9999
# Check Item Pass Fail Notes / Severity
3.1 Service penetrations through fire walls/floors are sealed
Pipes, cables, ducts, trays — check both sides of barrier
3.2 Fire stopping material is appropriate and correctly installed
Intumescent sealant, batt, collars, wraps — third-party certified
3.3 Riser cupboards — fire stopping intact at each floor level
No gaps, no missing fire stopping, access panels in place
3.4 Ceiling voids — compartment barriers extend to underside of slab
No gaps above corridor/compartment walls
3.5 No unauthorised alterations breaching compartment lines
New installations, removed walls, unplugged openings
4. Means of Escape
# Check Item Pass Fail Notes / Severity
4.1 Escape routes clear and unobstructed
No storage, furniture, or items narrowing corridors below 1m
4.2 Final exit doors open without a key from inside
Panic hardware / push bars operational
4.3 Emergency lighting operational
Check indicator LEDs, last test date recorded
4.4 Fire exit and directional signs visible and illuminated
Green running man signs at every change of direction
5. Fire Signage
# Check Item Pass Fail Notes / Severity
5.1 "Fire Door Keep Shut" on every fire door without a hold-open device
5.2 "Fire Door Keep Locked" on every locked fire door
5.3 Fire action notices posted in visible locations
At main entrance, each floor, near fire alarm call points
5.4 Fire extinguisher ID signs present and correct type indicated
6. Documentation & Records Ref: Fire Safety Order 2005, Article 9
# Check Item Yes No Notes / Action Required
6.1 Current fire risk assessment on file (within last 12 months or after significant change)
6.2 Fire door inspection records on file
6.3 Remedial works log — actions tracked and closed out
6.4 Fire alarm test records up to date (weekly test)
6.5 Emergency lighting test records up to date (monthly flick test, annual 3-hour test)
6.6 Fire evacuation drill conducted and recorded (at least annually)

Additional Notes / Priority Actions